The circuit for the hot water sensor TW1 is shorted, indicated by resistance below 390 Ohm.
Click steps to track your progress.
Disconnect the sensor from the installer board.
Measure the resistance and compare it to the sensor table in the documentation.
Repair the cable or replace the sensor if necessary.
If the warning persists after sensor replacement, the installer board may be defective and require replacement.