5409

Warning Z1 Air inlet sensor TL2 short circuit — Air sensor shorted

Bosch · Alarm List A/W Split (8754) 2018 01 10

What does 5409 mean?

This warning indicates that the circuit for the air inlet sensor TL2 is shorted (less than 900 Ohm).

Common Causes

  • The circuit for air inlet sensor TL2 or its signal cable is shorted.
  • Defective I/O module.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Measure the sensor's resistance and compare it to the values in the sensor table in the documentation.

  2. 2

    If the resistance is too low, check the signal cable for damage or a short.

  3. 3

    If the sensor itself is faulty, replace TL2. If the issue persists, consider replacing the I/O module.