5410

Alarm Z1 Air inlet sensor TL2 fault — Air sensor failure

Bosch · Alarm List A/W Split (8754) 2018 01 10

What does 5410 mean?

This alarm is triggered if 3 warnings (codes 5408, 5409) occur within 2 hours, or if the sensor TL2 is continuously shorted or broken for 15 minutes.

Common Causes

  • Problems with the air inlet sensor TL2 or its connection.
  • Issues with the I/O module.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Disconnect sensor TL2 from the installer module and check the Ohm value for the sensor and cable.

  2. 2

    Compare the measured values to the sensor table in the documentation.

  3. 3

    If the sensor or cable readings are abnormal, replace the sensor or repair the cable.

  4. 4

    If readings are normal but the alarm persists, the I/O module may need replacement.

Browse all codes in this manual (60)
Verified technical data. Last updated: April 2026