Bosch · Alarm List A/W Split (8754) 2018 01 10
This warning is issued if the temperature of JR0 drops below the allowed range (below -27°C) for more than 30 seconds. It suggests a blockage or low airflow in the air heat exchanger.
Click steps to track your progress.
Ensure sufficient airflow through the air heat exchanger.
Check if 230V voltage is available on output PL3, terminal 32 (78, N).
Check the 0-10V voltage on output PL3 PWM, terminal 20 (20, 26) using the test function for the outdoor unit.
Check control cables to the expansion valves and run a test cycle to verify they open.
If voltages are missing, replace the I/O module. If voltages are present but the fan doesn't run, replace the fan.