5515

Alarm Z1 Evap. Pressure on JR0 too low — Evaporator pressure failure

Bosch · Alarm List A/W Split (8754) 2018 01 10

What does 5515 mean?

This alarm is triggered after 3 warnings (code 5514) within 3 hours, or if the warning persists for 30 minutes, specifically during cooling mode. It indicates a persistent issue with low evaporator pressure.

Common Causes

  • Blocked or low airflow through the air heat exchanger.
  • Missing fan voltage or control signal.
  • Stuck expansion valve.
  • Defective I/O module.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Ensure adequate airflow through the air heat exchanger.

  2. 2

    Verify the presence of 230V supply voltage and the 0-10V control signal for the fan.

  3. 3

    Check the control cables and operation of the expansion valves.

  4. 4

    Replace the I/O module if voltages are missing, or the fan if voltages are present but it doesn't run.

Browse all codes in this manual (60)
Verified technical data. Last updated: April 2026