This alarm is triggered after 3 warnings (code 5514) within 3 hours, or if the warning persists for 30 minutes, specifically during cooling mode. It indicates a persistent issue with low evaporator pressure.
Click steps to track your progress.
Ensure adequate airflow through the air heat exchanger.
Verify the presence of 230V supply voltage and the 0-10V control signal for the fan.
Check the control cables and operation of the expansion valves.
Replace the I/O module if voltages are missing, or the fan if voltages are present but it doesn't run.