Bosch · Compress 7000 Heat Pumps
This alarm is triggered if the installer has selected an external room temperature sensor module to control heating circuit 2, but this module has not been developed or is not physically connected.
Click steps to track your progress.
Access the Service menu on your system controller.
Navigate to 'Set heating/cooling' -> 'Heating circ. 2'.
Set 'Ext. room temp. sensor' to 'No'. Ensure 'Programming unit' for Heating circ. 2 is set to 'RC100/CR10'.