CodeRegistry
Brands
  1. Home
  2. Bosch
  3. Compress 7000 Heat Pumps
  4. 5252
About·Privacy·Terms

CodeRegistry — Your global library for technical solutions.

For your safety: always follow the equipment manufacturer’s official manuals. CodeRegistry is an independent help site and is not affiliated with the brands listed here.

5252

Warning Z1 Restr. in flow rate btw. outdoor and ind. unit (check strainer) — Restricted flow rate

Bosch · Compress 7000 Heat Pumps

What does 5252 mean?

This warning appears when the heat carrier temperature difference (delta) exceeds 13K in heating mode or 7K in cooling mode. This suggests restricted flow or poor circulation within the heating system.

Common Causes

  • Bad circulation in the heating carrier/heating system.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Check all adjustment valves and thermostats within your heating system to ensure they are open and functioning correctly.

  2. 2

    Inspect the system for any potential blockages or closed valves that could restrict flow.

  3. 3

    Ensure the system is properly filled and de-aired to support good circulation.

Browse all codes in this manual (60)
Verified technical data. Last updated: April 2026

Related Faults

1001/A2xNo communication betw. system controller and remote control — Room sensor error A21-A241010No communication via EMS BUS connection — Device not receiving EMS token1051No communication with external room temp. sensor module — Incorrect software setting for heating circuit 1
Source: Bosch Compress 7000 Heat Pumps
Open Manual (Page 12)Search more codes in this manual