Bosch · Compress 7000 Heat Pumps
This alarm indicates that communication with the compressor control system is missing, or more than 30% of data sent to the inverter returns with errors. This can be caused by power issues, incorrect settings, or cable interference.
Click steps to track your progress.
Check the 230V/400V connections in both the indoor and outdoor units for secure connections.
Verify the P-selector setting on the I/O module matches your Heat Pump model (P=4 for 13 kW 3N~, P=6 for 13 kW 1N~).
If the alarm persists, contact a qualified technician to check MODbus and CANbus cabling for connections and proper routing, ensuring cables are separated from supply voltage by at least 100 mm.