Bryant · Comfort Alert Diagnostic Module
The system's discharge pressure is out of limits, or the compressor has overloaded. This is a LOCKOUT condition.
Click steps to track your progress.
Turn off unit power supply and install a lockout tag.
Check for high head pressure readings.
Clean the condenser coil if it is dirty or blocked.
Verify the condenser fan motor is operating correctly.
If a low pressure switch is present and open, refer to Flash Code 3 troubleshooting.