10095

10095 — Free cooling operation failure, circuit B

Carrier · 30XA/XAS/XB/XBP/XW Chillers

What does 10095 mean?

Free cooling operation on circuit B has failed. Circuit B will shut down, but free cooling can restart after 30 minutes. This may be due to a refrigerant pump fault.

Common Causes

  • Refrigerant pump fault
  • Connection problems on circuit B

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Verify the refrigerant pump is functioning correctly.

  2. 2

    Check the wiring for circuit B related to free cooling.

  3. 3

    Contact Carrier Service if free cooling operation does not resume.