3 Fault Code

Fault Code 3 — DEV OVERTEMP

Carrier · Energy Recovery Ventilators

What does 3 Fault Code mean?

The drive's heat sink is overheated, reaching or exceeding 115°C (239°F).

Common Causes

  • Fan failure
  • Obstructions in airflow
  • Dirt or dust on the heat sink
  • Excessive ambient temperature
  • Excessive motor load

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Check if the drive's cooling fan is operating.

  2. 2

    Remove any obstructions blocking airflow to the heat sink.

  3. 3

    Clean the heat sink of any dirt or dust.

  4. 4

    Ensure the ambient temperature is within the drive's operating limits.

  5. 5

    Reduce the motor load if it is excessively high.

  6. 6

    Reset the VFD after correcting the issue.