Bosch · Alarm List A/W Split (8754) 2018 01 10
This alarm is triggered after 3 warnings (code 5514) within 3 hours, or if the warning persists for 30 minutes, specifically during cooling mode. It indicates a persistent issue with low evaporator pressure.
Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.
Ensure adequate airflow through the air heat exchanger.
Verify the presence of 230V supply voltage and the 0-10V control signal for the fan.
Check the control cables and operation of the expansion valves.
Replace the I/O module if voltages are missing, or the fan if voltages are present but it doesn't run.