Bryant · Comfort Alert Diagnostic Module
The module is not receiving power, which prevents it from monitoring the system or controlling the compressor.
Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.
Turn off unit power supply and install a lockout tag.
Verify that the R and C module terminals are connected.
Check for 24VAC voltage at the module's R and C terminals.
Ensure the R and C terminals receive power directly from the control transformer.
Confirm the module is not powered by another device that could interrupt the 24VAC supply.