Lennox · EL18KSLV Series Outdoor Units
The high pressure switch circuit has been detected as open for 30 seconds after 5 minutes of compressor run time. This indicates a potential issue with system pressure or the switch itself.
Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.
Power off the unit and check if the pressure switch connection is secure.
Use a multimeter to check if the high pressure switch terminal is short-circuited.
Check if the Electronic Expansion Valve (EEV) coil is fixed well.
Ensure the stop valve is open.
Use a multimeter to check the resistance of Tc & Te.
Inspect the piping system for clogs and clean if necessary.