CodeRegistry
Marken
  1. Startseite
  2. York
  3. Smart Equipment Control
  4. HS2 Off Due to Gas Valve
About·Privacy·Terms

CodeRegistry — Ihre globale Bibliothek für technische Lösungen.

Zu Ihrer Sicherheit: Befolgen Sie immer die offiziellen Herstellerhandbücher. CodeRegistry ist unabhängig und steht in keiner Verbindung zu den genannten Marken.

HS2 Off Due to Gas Valve

HS2 Off Due to Gas Valve alarm

York · Smart Equipment Control

Was bedeutet HS2 Off Due to Gas Valve ?

This alarm indicates that the heating stage 2 (HS2) is disabled because of an issue related to the gas valve. This could be due to a lack of a command signal or a problem with the gas valve system.

Häufige Ursachen

  • No 24 VAC power at the W2 input when heat is commanded
  • The H2 output is not commanding 24 VAC to the ignition control module
  • Problem with the 24 VAC for outputs terminal
  • Faulty ignition control module or gas valve
  • Voltage leak on the W2 terminal
  • Incorrect LV phasing if two transformers are installed

Reparaturschritte & Checkliste

Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.

  1. 1

    If using a 24 VAC input, check for 24 VAC at the W2 input when a heat command is active. If not using a 24 VAC input, verify the space temperature is below the heating set point.

  2. 2

    Check if the H2 output is commanding 24 VAC to the ignition control module. If not, check the 24 VAC for outputs terminal.

  3. 3

    If power is not present at H2 or the outputs terminal, trace the wiring for power loss. If power is present, check the ignition control module and gas valve.

  4. 4

    Verify the ignition control module is completing its sequence correctly. Check for MV feedback.

  5. 5

    If using a 24 VAC input to W2, ensure there is no voltage leak (even 0.5 VAC can cause issues).

  6. 6

    If two transformers are installed, verify the LV phasing.

Alle Codes in diesem Handbuch durchsuchen (17)
Verifizierte technische Daten. Zuletzt aktualisiert: April 2026

Verwandte Fehlercodes

Building Pressure Sensor FailureBuilding Pressure Sensor Failure alarmC1 Locked Out Due to High PressureRefrigeration Circuit 1 High Pressure LockoutC2 Locked Out Due to High PressureRefrigeration Circuit 2 High Pressure Lockout
Quelle: YORK Smart Equipment Control
Open Manual (Page 12)Mehr Codes in diesem Handbuch suchen