HS3 Off Due to Gas Valve

HS3 Off Due to Gas Valve alarm

York · Smart Equipment Control

Was bedeutet HS3 Off Due to Gas Valve ?

This alarm means that heating stage 3 (HS3) is deactivated due to an issue with the gas valve. It could be related to the command signal for heating or the gas valve's operational status.

Häufige Ursachen

  • No 24 VAC power at the W3 input when heat is commanded
  • The H3 output is not commanding 24 VAC to the ignition control module
  • Problem with the 24 VAC for outputs terminal
  • Faulty ignition control module or gas valve
  • Voltage leak on the W3 terminal
  • Incorrect LV phasing if two transformers are installed

Reparaturschritte & Checkliste

Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.

  1. 1

    If using a 24 VAC input, check for 24 VAC at the W3 input when a heat command is active. If not using a 24 VAC input, verify the space temperature is below the heating set point.

  2. 2

    Check if the H3 output is commanding 24 VAC to the ignition control module. If not, check the 24 VAC for outputs terminal.

  3. 3

    If power is not present at H3 or the outputs terminal, trace the wiring for power loss. If power is present, check the ignition control module and gas valve.

  4. 4

    Verify the ignition control module is completing its sequence correctly. Check for MV feedback.

  5. 5

    If using a 24 VAC input to W3, ensure there is no voltage leak (even 0.5 VAC can cause issues).

  6. 6

    If two transformers are installed, verify the LV phasing.

Alle Codes in diesem Handbuch durchsuchen (17)