ALERT LED 5 flashes Yellow

Yellow ALERT LED 5 flashes — Open circuit

Bryant · Comfort Alert Diagnostic Module

¿Qué significa ALERT LED 5 flashes Yellow ?

An open circuit has been detected in the system, preventing proper operation. This could be due to power supply issues or component failure.

Causas comunes

  • Condensing unit power disconnect is open.
  • Compressor circuit breaker or fuses are open.
  • Compressor contactor has failed open.
  • High pressure switch is open and requires manual reset.
  • Broken supply wires or connector.
  • Unusually long compressor protector reset time due to extreme ambient temperature.
  • Compressor windings are damaged.

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Turn off unit power supply and install a lockout tag.

  2. 2

    Verify the condensing unit power disconnect is closed.

  3. 3

    Check compressor circuit breakers or fuses.

  4. 4

    Inspect for broken supply wires or loose connectors.

  5. 5

    If a high pressure switch is open, attempt a manual reset.

  6. 6

    Consider extreme ambient temperatures affecting protector reset time.