CodeRegistry
Marcas
  1. Inicio
  2. GE Appliances
  3. Air Conditioning
  4. P6
About·Privacy·Terms

CodeRegistry — Tu biblioteca global de soluciones técnicas.

Por su seguridad, siga siempre los manuales oficiales del fabricante. CodeRegistry es un sitio independiente y no está afiliado a las marcas citadas.

P6

P6 - Master control and driver communication error

GE Appliances · Air Conditioning

¿Qué significa P6 ?

Communication between the master control board and the driver board has been interrupted for 30 seconds. This fault will cause the system to shut down for protection. The ODU main board LED will display this error.

Causas comunes

  • Communication wire between master control and driver is not well connected, or has bad contact, or is broken
  • The switch power of drive board is abnormal, causing abnormal 3.3V power voltage
  • Communication circuit of the drive board or the master control board is abnormal

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Check the communication wire between the master control and driver for proper connection. Reconnect or replace the wire if it's loose, badly connected, or broken.

  2. 2

    Verify the 3.3V power voltage from the drive board's switch power supply.

  3. 3

    Replace the drive board if its communication circuit is abnormal.

  4. 4

    Replace the master control board if its communication circuit is abnormal.

Ver todos los códigos en este manual (62)
Datos técnicos verificados. Última actualización: April 2026

Fallas relacionadas

1Error 1 — Outdoor PCB EEPROM fault10Error 10 — Defrost sensor fault11Error 11 — Compressor suction temperature sensor fault
Fuente: GE Appliances Air Conditioning
Open Manual (Page 33)Buscar más códigos en este manual