CodeRegistry
Marcas
  1. Inicio
  2. Lennox
  3. EL18KSLV Series Outdoor Units
  4. [42]
About·Privacy·Terms

CodeRegistry — Tu biblioteca global de soluciones técnicas.

Por su seguridad, siga siempre los manuales oficiales del fabricante. CodeRegistry es un sitio independiente y no está afiliado a las marcas citadas.

[42]

Error 42 — Open high pressure switch

Lennox · EL18KSLV Series Outdoor Units

¿Qué significa [42] ?

The high pressure switch circuit has been detected as open for 30 seconds after 5 minutes of compressor run time. This indicates a potential issue with system pressure or the switch itself.

Causas comunes

  • Incorrect pressure switch wiring.
  • Abnormal system pressure.
  • The system is clogged.
  • Incorrect refrigerant charge.
  • A valve is malfunctioning.
  • The pressure switch is faulty.
  • The main control board (PCB) is faulty.

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Power off the unit and check if the pressure switch connection is secure.

  2. 2

    Use a multimeter to check if the high pressure switch terminal is short-circuited.

  3. 3

    Check if the Electronic Expansion Valve (EEV) coil is fixed well.

  4. 4

    Ensure the stop valve is open.

  5. 5

    Use a multimeter to check the resistance of Tc & Te.

  6. 6

    Inspect the piping system for clogs and clean if necessary.

Ver todos los códigos en este manual (43)
Datos técnicos verificados. Última actualización: April 2026

Fallas relacionadas

1Error 1 — EEPROM malfunction or damage10Error 10 — Outdoor defrost sensor failure11Error 11 — Suction temperature sensor failure
Fuente: Lennox EL18KSLV Series Outdoor Units
Open Manual (Page 76)Buscar más códigos en este manual