[43]

Error 43 — Open low pressure switch

Lennox · EL18KSLV Series Outdoor Units

¿Qué significa [43] ?

The low pressure switch circuit has been detected as open for 60 seconds (after 5 minutes of compressor run time) or for 30 seconds during standby. This suggests a problem with system pressure or the switch.

Causas comunes

  • Incorrect pressure switch wiring.
  • Abnormal system pressure.
  • The system is clogged.
  • Incorrect refrigerant charge.
  • A valve is malfunctioning.
  • The pressure switch is faulty.
  • The main control board (PCB) is faulty.

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Power off the unit and check if the pressure switch connection is secure.

  2. 2

    Use a multimeter to check if the low pressure switch terminal is short-circuited.

  3. 3

    Check if the Electronic Expansion Valve (EEV) coil is fixed well.

  4. 4

    Ensure the stop valve is open.

  5. 5

    Use a multimeter to check the resistance of Tc, Te, and Ts.

  6. 6

    Inspect the piping system for clogs and clean if necessary.

Ver todos los códigos en este manual (43)