Lennox · PRODIGY 2.0 Unit Controller
This alarm is triggered when the damper actuator does not move the damper to the target position within the predefined time, meaning the control voltage does not match the feedback voltage within the acceptable tolerance.
Haga clic en los pasos para seguir su progreso.
Check for any physical obstructions preventing damper movement.
Inspect the damper actuator for signs of damage or wear.
Verify the control voltage supplied to the actuator.
Ensure wiring connections are secure.
If the fault persists, the damper actuator or damper mechanism may need replacement.