Lennox · PRODIGY 2.0 Unit Controller
This alarm is triggered when the actual outdoor air intake is greater than the target outdoor air percentage (set by Parameter 240) for a specified duration (set by Parameter 244).
Haga clic en los pasos para seguir su progreso.
Inspect the outdoor air damper for correct operation and position.
Check for any obstructions or unusual conditions affecting outdoor air intake.
Verify the outdoor air sensor readings.
Review the settings for Parameter 240 (Advanced Air Flow High Outdoor CFM Alarm Set Point) and Parameter 244 (duration).
Ensure the system is correctly configured for outdoor air intake.