Jumper missing for ZSI

Short-time and ground-fault delays are zero due to missing ZSI jumper

Schneider Electric · Micrologic Control units 2.0 A, 5.0 A, 6.0 A, 7.0 A St

¿Qué significa Jumper missing for ZSI ?

If the circuit breaker is equipped for ZSI protection but the protection function is not used, a jumper must be installed. Without it, the short-time and ground-fault tripping delays will be set to zero, preventing proper discrimination.

Causas comunes

  • The required jumper for ZSI protection has not been installed.
  • Circuit breaker is configured for ZSI but the function is not intended to be used.

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Ensure the protection function is not used on circuit breakers equipped for ZSI.

  2. 2

    Install a jumper to short terminals Z3, Z4, and Z5.

  3. 3

    Verify the jumper is securely in place.

  4. 4

    Check the trip unit settings to confirm delays are now active.

Ver todos los códigos en este manual (19)
Datos técnicos verificados. Última actualización: April 2026