ESS Relay test Pending

ESS Relay test Pending — Feed-in disabled until test completes

SolarEdge · ESS Systems

¿Qué significa ESS Relay test Pending ?

The system is in the process of performing a required relay test before it can begin feeding power from the battery or solar to loads or the grid. During this test, the system needs to run in inverter mode.

Causas comunes

  • The system has just been connected or restarted, and the relay test is initiated.
  • Battery voltage is too low to complete the relay test.
  • The ESS Assistant is installed and requires this initial test.

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Ensure the battery has sufficient charge (e.g., above 14/28/56 volts or 20% SOC).

  2. 2

    Allow the system time to complete the test, which typically takes about 1 minute.

  3. 3

    Check the 'ESS Relay test' status in the Multi/Quattro's Advanced submenu on the device list. It should change from 'Pending' to 'Completed'.

  4. 4

    If the test repeatedly fails, check battery health and connections.

Ver todos los códigos en este manual (12)
Datos técnicos verificados. Última actualización: April 2026

Fallas relacionadas

Battery discharging then charged every nightBattery discharging then charged every night — Potential Sustain protection or SOC settingInput current-limit settingInput current-limit setting — Loads must be on AC-out for limiter to workLoads powered by grid, not battery or solarLoads powered by grid, not battery or solar — Check battery SOC, limits, and relay test