Dirty Filter Switch Trip

Dirty Filter Switch Trip alarm

York · Smart Equipment Control

¿Qué significa Dirty Filter Switch Trip ?

This alarm is activated when the dirty filter switch (DFS) closes, sending a 24 VAC signal to the SEC board. It indicates that the air filters need to be changed.

Causas comunes

  • Dirty or clogged air filters
  • Blocked or incorrectly installed port tubes on the DFS switch
  • High return static pressure
  • Faulty DFS switch
  • Faulty SEC board

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Check and clean or replace the air filters. If they are clean, proceed to the next steps.

  2. 2

    Ensure the DFS switch's port tubes are correctly installed and not blocked.

  3. 3

    Check for a 24 VAC input to the SEC board's DFS input, which should trigger the alarm if the switch is closed.

  4. 4

    If the switch is closed and everything else is okay, check the return static pressure. If it exceeds 0.2 in. w.c., address the cause of high static pressure.

  5. 5

    If the SEC board shows the alarm with no 24 VAC input and all other checks are clear, power cycle the unit. If the alarm persists, replace the SEC board.

Ver todos los códigos en este manual (17)