The inverter has detected an electric arc, indicating a fault on the DC side. This safety measure interrupts the grid power feed for at least 5 minutes to prevent overheating and fire risk. If multiple arcs are detected within 24 hours, the grid power feed can be permanently interrupted until manually reconnected.
Click steps to track your progress.
Carefully check all DC plug connections to ensure they are correct, secure, and free from damage.
Repair any faulty insulation correctly and in line with installation instructions.
Ensure all DC connection work was performed according to the inverter's installation guidelines.
If the issue persists or multiple arcs are detected, a manual reconnection may be required after resolving the underlying cause.
Consider if any active PV module electronics are affecting the AFCI operation.