8

OPERATION INDICATOR lamp blinks 8 times (Pattern A) - Compressor overcurrent interruption / Abnormality of power module

MHI · Air Conditioning

What does 8 mean?

The OPERATION INDICATOR lamp blinks eight times in 'Output pattern A' from the indoor unit. This points to either a compressor overcurrent or an abnormality within the power module.

Common Causes

  • Compressor overcurrent interruption.
  • Abnormality or fault in the power module.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Check for looseness, disconnection, or incorrect connection of the compressor wiring.

  2. 2

    Measure the resistance values among the terminals on the compressor using a tester.

  3. 3

    Inspect the power module on the outdoor unit for any visible damage or loose connections.

  4. 4

    If the issue persists, a qualified technician should assess the power module and compressor.

Browse all codes in this manual (124)
Verified technical data. Last updated: April 2026

Related Faults

00Outdoor Board LED only green lights up after startup - No outdoor unit of address 0 / Remote controller transmission wire open1OPERATION INDICATOR lamp blinks 1 time (Pattern A) - Indoor/outdoor unit communication error (Transmitting error - Outdoor unit)14OPERATION INDICATOR lamp blinks 14 times (Pattern A) - Other errors
Source: MHI Air Conditioning
Open Manual (Page 23)Search more codes in this manual