U3, U4

Outdoor Board LED1 (green) blinks four times and LED2 (red) blinks three times alternately - Abnormality of power module

MHI · Air Conditioning

What does U3, U4 mean?

During startup or operation, the outdoor unit's LED1 (green) blinks four times and LED2 (red) blinks three times alternately, indicating an abnormality within the power module.

Common Causes

  • Abnormality of power module.
  • Faulty power module components.
  • Power supply issues affecting the module.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Check for looseness, disconnection, or incorrect connection of the compressor wiring, as power module issues can impact the compressor.

  2. 2

    Measure resistance values among terminals on the compressor using a tester to rule out related issues.

  3. 3

    Ensure the power supply voltage is stable and within specifications.

  4. 4

    If the error persists, the power module likely requires professional inspection or replacement.

Browse all codes in this manual (124)
Verified technical data. Last updated: April 2026

Related Faults

00Outdoor Board LED only green lights up after startup - No outdoor unit of address 0 / Remote controller transmission wire open1OPERATION INDICATOR lamp blinks 1 time (Pattern A) - Indoor/outdoor unit communication error (Transmitting error - Outdoor unit)14OPERATION INDICATOR lamp blinks 14 times (Pattern A) - Other errors