Mitsubishi Electric · Air Conditioning
This fault is related to the liquid pipe thermistor (TH2), indicating it may be disconnected, have an open circuit, or a short circuit.
Click steps to track your progress.
Ensure the TH2 thermistor is properly connected.
Examine the wiring connected to TH2 for damage or loose connections.
Measure the resistance of the TH2 thermistor (consult manual for values).
Replace the TH2 thermistor if found to be defective.