Mitsubishi Electric · MSZ-AY Air Conditioners
The indoor unit and outdoor unit do not operate because the serial signal from the outdoor unit has not been received for 6 minutes. This can also happen if a non-low-standby-power outdoor unit was previously connected, and a low-standby-power model is now in use. It can also be caused by miswiring or interference.
Click steps to track your progress.
Turn OFF the power supply to the unit at the circuit breaker, wait for a few minutes, then turn it back ON.
Press the emergency operation switch on the indoor unit.
Turn OFF any inverter-controlled lighting equipment nearby, or re-position the unit/light to reduce interference.
Check all indoor/outdoor connecting wires for miswiring, damage, or poor contact.
If a low-standby-power model is now connected, clear the error history by referring to 'Deleting the memorized abnormal condition' (10-2.1) in the full manual.
Refer to the 'How to check miswiring and serial signal error' section (10-6) in the full manual for detailed checks.