Mitsubishi Electric · MSZ-FH Air Conditioners
When in failure mode recall function, the POWER lamp flashes two times, followed by a 2.5-second OFF period. This indicates a short or open circuit in the indoor coil thermistor (main or sub) detected during operation.
Click steps to track your progress.
Refer to the characteristics of the main and sub indoor coil thermistors (10-7. in the manual) for more details.
Check the wiring and connections of the indoor coil thermistors for any visible damage or looseness.
Release the failure mode recall function by cycling power or pressing the remote controller's RESET button.