Wired remote control wiring error — RUN LED OFF, TIMER LED flashes 5 times

Mitsubishi Heavy Industries · Air Conditioners

What does 05 mean?

The system cannot receive signals from the wired remote control for 35 seconds. This indicates a problem with the remote control wiring, the remote control unit, or the indoor PCB.

Common Causes

  • Broken wired remote control wire (specifically the Y wire being open)
  • X and Y wires of the remote control are reversely connected
  • Electrical noise penetrating the wired remote control lines
  • Faulty wired remote control unit or indoor PCB

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Turn off the main power to the unit before inspecting wiring.

  2. 2

    Inspect the wired remote control cable for any signs of breakage or damage, paying close attention to the Y wire.

  3. 3

    Verify that the X and Y wires for the remote control are connected correctly at the terminals and are not reversed.

  4. 4

    Check for any external sources of electrical noise that might be interfering with the remote control lines.

  5. 5

    Ensure all remote control wiring connections are firm and secure.