Low room temperature

Low Room Temperature — House is not warm enough

NIBE · F1245 Ground Source Heat Pumps

What does Low room temperature mean?

The room temperature is lower than desired, indicating that the heating system is not effectively warming the space.

Common Causes

  • Thermostats in several rooms are closed or set too low.
  • Heat pump is in an incorrect operating mode.
  • Too low set value on the automatic heating control or heating curve.
  • Too low or no operating prioritization of heat.
  • Holiday mode is activated.
  • External switch for changing room heating is activated.
  • Circulation pump(s) (GP1 and/or GP2) are stopped.
  • Air is present in the climate system.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Set thermostats to maximum in as many rooms as possible. Adjust the room temperature using menu 1.1 instead of choking thermostats.

  2. 2

    Check the heat pump's operating mode in menu 4.2. If 'auto' is selected, increase 'stop heating' in menu 4.9.2. If 'manual' is selected, choose 'heating'; if insufficient, select 'addition'.

  3. 3

    Go to menu 1.1 (temperature) and adjust the heat curve offset. If the room temperature is only low in cold weather, adjust the curve slope in menu 1.9.1 (heating curve) upwards.

  4. 4

    In menu 4.9.1, increase the time heating is prioritized.

  5. 5

    Check menu 1.3.4 and ensure 'Holiday mode' is set to 'Off'.