Panasonic · Aquarea Heat Pumps
This mode is used to extract all refrigerant from the piping into the outdoor unit, typically for relocation or disposal. The 3-way valve will shift to the room side.
Click steps to track your progress.
Press the SERVICE S/W for 5 seconds to enter Service mode.
Select Sr:01 and press SET S/W to start the Pump Down operation.
Allow the operation to complete as per the manual's timing instructions.
Press the ON/OFF button to stop the unit after pump down.
Note: Low Pressure error and Freeze prevention judgments are suspended during this operation.