Samsung AC & Climate Systems

60 fault codes documented

101

Error 101 — Indoor unit communication error

The indoor unit cannot receive data from the outdoor unit. This indicates a communication problem between the two main components of the system.

102

Error 102 — Communication error between indoor and outdoor units

There is a communication error between the indoor unit and the outdoor unit. This message is typically displayed on the indoor unit.

108

Error 108 — Repeated address setting

This error occurs when two or more devices in the system have been assigned the same address. Each device needs a unique address to communicate properly.

110

Error 110 — Communication error between Hydro unit and Control kit

This error indicates a communication failure between the Hydro unit's main circuit board (PBA) and the Control kit's circuit board (PBA).

121

Error 121 — Indoor unit temperature sensor error (Short or Open)

The temperature sensor inside the indoor unit is either short-circuited or has an open connection. This prevents accurate temperature readings.

122

Error 122 — Indoor unit EVA IN sensor error (Short or Open)

The EVA IN temperature sensor for the indoor unit has a short circuit or an open connection, affecting temperature readings for that specific sensor.

123

Error 123 — Indoor unit EVA OUT sensor error (Short or Open)

The EVA OUT temperature sensor for the indoor unit is experiencing a short circuit or an open connection, impacting temperature monitoring.

128

Error 128 — Indoor unit EVA IN temperature sensor detached

The EVA IN temperature sensor has become detached from the EVA IN pipe. This will lead to inaccurate temperature readings.

129

Error 129 — Indoor unit EVA OUT temperature sensor detached

The EVA OUT temperature sensor has detached from its designated pipe. This will cause incorrect temperature measurements.

130

Error 130 — Indoor unit heat exchanger in/out sensors detached

Both the heat exchanger inlet and outlet temperature sensors have become detached. Accurate heat exchange monitoring is compromised.

135

Error 135 — Indoor unit cleaning fan RPM feedback error

The system is not receiving correct speed (RPM) feedback from the indoor unit's cleaning fan. This may affect the fan's performance or operation.

151

Error 151 — Opened EEV error (2nd detection)

The Electronic Expansion Valve (EEV) in the indoor unit is detected as being open when it should not be. This is the second detection of this issue.

152

Error 152 — Closed EEV error (2nd detection)

The Electronic Expansion Valve (EEV) in the indoor unit is detected as being closed when it should not be. This is the second detection of this problem.

153

Error 153 — Floating switch error (2nd detection)

The floating switch, likely related to condensate drainage, has triggered an error. This is the second time this error has been detected.

154

Error 154 — Indoor unit RPM feedback error

The system is not receiving proper speed (RPM) feedback from a component within the indoor unit. This could affect the unit's overall operation.

161

Error 161 — Mixed operation mode error

This error occurs when the outdoor unit is preparing for cooling (or heating) and one or more indoor units are attempting to operate in the opposite mode (heating or cooling).

162

Error 162 — EEPROM error of MICOM

There is an error with the EEPROM memory on the MICOM (microcontroller) unit. This usually indicates a physical problem with the component or its circuit.

163

Error 163 — Incorrect or missing remote controller option input

The indoor unit's remote controller has an incorrect setting or is missing required input. Alternatively, the outdoor unit's EEPROM data may be corrupted.

180

Error 180 — Simultaneous opening of cooling/heating MCU SOL V/V (1st detection)

The system has detected, for the first time, that both the cooling and heating solenoid valves (SOL V/V) controlled by the MCU are open simultaneously. This should not happen.

181

Error 181 — Simultaneous opening of cooling/heating MCU SOL V/V (2nd detection)

This is the second detection of an error where both the cooling and heating solenoid valves are open at the same time. This indicates a persistent problem.

185

Error 185 — Cross wiring error between communication and power cable

The communication cable and the power cable for the indoor unit have been crossed or improperly wired together.

186

Error 186 — Connection error or problem on SPi

There is a connection error or a general problem with the SPi interface. The SPi is a communication protocol or interface used by the system.

190

Error 190 — No temperature changes in EVA IN during pipe inspection or incorrect temperature

During pipe inspection, no temperature change is detected at the EVA IN sensor, or the temperature reading is incorrect. This could also be related to a wrong unit address.

191

Error 191 — No temperature changes in EVA OUT during pipe inspection or incorrect temperature

The EVA OUT sensor does not show a temperature change during pipe inspection, or it reports an incorrect temperature. This might also be due to a wrong unit address.

198

Error 198 — Disconnected thermal fuse

The thermal fuse within the indoor unit has been disconnected or has blown. This is a safety feature that cuts power if overheating occurs.

201

Error 201 — Communication error between indoor and outdoor units

A communication error exists between the indoor and outdoor units. This can be caused by installation number settings, repeated indoor unit addresses, or cable issues.

202

Error 202 — Communication error between indoor and outdoor units (all units)

A communication error is affecting all indoor units communicating with the outdoor unit. This typically points to an issue with the outdoor unit's communication cable or system.

203

Error 203 — Communication error between main and sub outdoor units

This error occurs when there is a communication problem between the main outdoor unit and a sub-outdoor unit in a multi-system setup.

205

Error 205 — Communication error on all PBA within outdoor unit C-Box

There is a communication error among all Printed Circuit Boards (PBAs) within the outdoor unit's Control Box (C-Box). This indicates a serious internal issue.

206

Error 206 — HUB/FAN/INV PBA communication error

Communication errors are detected on specific Printed Circuit Boards (PBAs) within the outdoor unit: HUB PBA, FAN PBA, or Inverter PBA (INV1/INV2). Specific error codes like E206-C001 indicate which PBA is affected.

211

Error 211 — Single indoor unit uses 2 MCU ports not in series

A single indoor unit is connected using two MCU ports that are not configured in series, which is an incorrect setup.

212

Error 212 — 3 or more indoor units have the same address

Three or more indoor units have been assigned the same address. Each unit must have a unique address for proper system communication.

396

Error 396 — DC voltage sensor error of Fan2

The DC voltage sensor for Fan 2 in the outdoor unit is reporting an error. This may affect the fan's speed control or operation.

399

Error 399 — Heat sink temperature sensor error of Fan2

The temperature sensor monitoring the heat sink of Fan 2 in the outdoor unit is reporting an error.

400

Error 400 — Overheat due to contact failure on IPM of Inverter PBA2

The outdoor unit's Inverter PBA2 has an IPM (Intelligent Power Module) that is overheating, likely due to a contact failure. This is a critical fault.

407

Error 407 — Compressor operation stop due to high pressure protection

The compressor has stopped operating because the system's high pressure protection has been activated. This is a safety measure to prevent damage.

410

Error 410 — Compressor operation stop due to low pressure protection or leakage

The compressor has stopped due to low pressure protection being triggered, which can be caused by refrigerant leakage or insufficient refrigerant charge.

416

Error 416 — Compressor operation stop due to discharge temperature protection

The compressor has stopped because its discharge temperature has exceeded safe limits, triggering protection controls.

425

Error 425 — Phase reversal or phase failure (3-phase unit)

For 3-phase outdoor units, this error indicates that the incoming power phases (R-S-T-N) are reversed or one phase is missing. This can damage the compressor.

428

Error 428 — Compressor operation stop due to abnormal compression ratio

The compressor has stopped because the ratio between its discharge and suction pressures is abnormal. This suggests an internal issue with the compressor or refrigerant circuit.

438

Error 438 — EVI (ESC) EEV leakage or internal leakage

The Enhanced Vapor Injection (EVI) Electronic Expansion Valve (EEV) is experiencing leakage, either externally or internally within the intercooler, or has an incorrectly inserted connector.

439

Error 439 — Error due to refrigerant leakage

The system has detected a refrigerant leak. This is a critical issue that requires immediate attention to prevent system damage and environmental harm.

440

Error 440 — Heating mode restriction due to high air temperature

Heating mode operation is restricted because the ambient air temperature is too high. The system prevents heating to avoid issues in such conditions.

441

Error 441 — Cooling mode restriction due to low air temperature

Cooling mode operation is restricted because the ambient air temperature is too low. Operating in cooling under these conditions can cause problems.

442

Error 442 — Refrigerant charging restriction in heating mode when air temperature is over 15 °C

Refrigerant charging is restricted during heating mode if the outdoor air temperature is above 15°C. This is a specific operational constraint.

443

Error 443 — Operation prohibited due to pressure drop

The system's operation is prohibited because a significant pressure drop has been detected. This indicates a potential issue within the refrigerant circuit.

445

Error 445 — CCH is detached

The CCH (likely referring to a specific component like a control chip or sensor) has become detached. This could affect the unit's control or monitoring functions.

446

Error 446 — Operation failure of Fan1

Fan 1 in the outdoor unit is not operating correctly. This could be due to a motor issue, electrical problem, or obstruction.

447

Error 447 — Motor wire of Fan1 is not connected

The motor wire for Fan 1 in the outdoor unit is not properly connected. This prevents the fan from operating.

448

Error 448 — Lock error on Fan1

Fan 1 in the outdoor unit is experiencing a lock error, meaning it is unable to rotate freely or is jammed.

452

Error 452 — ZPC detection circuit problem or power failure

There is an issue with the ZPC (Zero Power Consumption) detection circuit, or a power failure affecting this circuit. This may impact specific functions of the unit.

453

Error 453 — Overheated motor of outdoor unit's Fan1

The motor of Fan 1 in the outdoor unit has overheated. This can be caused by prolonged operation, lack of airflow, or an internal motor fault.

455

Error 455 — Overheated IPM of Fan1

The Intelligent Power Module (IPM) associated with Fan 1 in the outdoor unit has overheated. This indicates a potential issue with the fan's power control.

461

Error 461 — Operation failure of inverter compressor 1

The inverter compressor (Compressor 1) is not operating correctly. This could be due to a motor fault, control issue, or power problem.

462

Error 462 — Compressor stop due to full current control or low current on CT2

The compressor has stopped operating due to either excessive current (full current control) or critically low current detected by CT2 (Current Transformer 2).

464

Error 464 — Over-current of inverter compressor 1

Inverter compressor 1 is drawing more current than its specified limits, triggering an over-current protection.

465

Error 465 — V-limit error of inverter compressor 1

Inverter compressor 1 has encountered a voltage limit error. This could mean the voltage supplied to the compressor is outside acceptable operational limits.

466

Error 466 — Over voltage / low voltage of inverter PBA1

The inverter PBA1 (Printed Board Assembly 1) is experiencing either overvoltage or undervoltage conditions. This can damage the PBA and connected components.

467

Error 467 — Unconnected wire of compressor 1

A wire connected to compressor 1 is not properly connected or has become disconnected. This will prevent the compressor from operating correctly.

468

Error 468 — Output current sensor error of inverter PBA1

The output current sensor on the inverter PBA1 is reporting an error. This sensor monitors the current supplied to the compressor, and its failure affects control.