Fault - ZSI related

Fault detected by upstream device

Schneider Electric · Micrologic Control units 2.0 A, 5.0 A, 6.0 A, 7.0 A St

What does Fault - ZSI related mean?

An upstream device has detected a fault. Depending on the settings, this may cause a delay in tripping to allow downstream devices to clear the fault.

Common Causes

  • A fault has occurred at point A or B in the system.
  • Incorrect ZSI settings (tripping delays set to zero).

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Check the wiring connections for the Zone Selective Interlocking (ZSI) system.

  2. 2

    Verify that the short-time and ground-fault tripping delays are not set to zero.

  3. 3

    Use the portable test kit to check the wiring and operation of the ZSI system.

  4. 4

    Consult the technical appendix for specific ZSI fault handling.