Schneider Electric · Micrologic Control units 2.0 A, 5.0 A, 6.0 A, 7.0 A St
An upstream device has detected a fault. Depending on the settings, this may cause a delay in tripping to allow downstream devices to clear the fault.
Click steps to track your progress.
Check the wiring connections for the Zone Selective Interlocking (ZSI) system.
Verify that the short-time and ground-fault tripping delays are not set to zero.
Use the portable test kit to check the wiring and operation of the ZSI system.
Consult the technical appendix for specific ZSI fault handling.