Jumper missing for ZSI

Short-time and ground-fault delays are zero due to missing ZSI jumper

Schneider Electric · Micrologic Control units 2.0 A, 5.0 A, 6.0 A, 7.0 A St

What does Jumper missing for ZSI mean?

If the circuit breaker is equipped for ZSI protection but the protection function is not used, a jumper must be installed. Without it, the short-time and ground-fault tripping delays will be set to zero, preventing proper discrimination.

Common Causes

  • The required jumper for ZSI protection has not been installed.
  • Circuit breaker is configured for ZSI but the function is not intended to be used.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Ensure the protection function is not used on circuit breakers equipped for ZSI.

  2. 2

    Install a jumper to short terminals Z3, Z4, and Z5.

  3. 3

    Verify the jumper is securely in place.

  4. 4

    Check the trip unit settings to confirm delays are now active.

Browse all codes in this manual (19)
Verified technical data. Last updated: April 2026