Schneider Electric · Micrologic Control units 2.0 A, 5.0 A, 6.0 A, 7.0 A St
Holding the 'menu' and 'arrow' buttons for four seconds allows you to access the first screen of the communication settings branch. A padlock icon indicates if the setting is locked.
Click steps to track your progress.
Press and hold the 'menu' and 'arrow' buttons simultaneously for four seconds.
Observe the display for the first communication settings screen.
If a padlock icon is closed, press the 'Quick View' button to unlock the setting.
The setting to be changed will flash, indicating it is ready for modification.