The display shows 'Fault 59' with a sub-code '201', indicating that the mass flow rate in the solar system for collector group 1 is too high.
Click steps to track your progress.
Adjust the mass flow in the solar system, for example, by decreasing the pump speed.
If applicable, close the flow restrictor on the solar station more.
Check and correct the settings for collector area, type, and climate zone in the Solar optimisation menu.