ALERT and TRIP LEDs flash together

Yellow and Red LEDs flashing together — Low control power input

Bryant · Comfort Alert Diagnostic Module

What does ALERT and TRIP LEDs flash together mean?

The control power supplied to the CADM is too low (below 19-28VAC), indicating a potential issue with the control transformer or its wiring.

Common Causes

  • Control circuit transformer issue.
  • Wiring problem to the control circuit.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Turn off unit power supply and install a lockout tag.

  2. 2

    Verify that the R and C terminals are supplied with 19-28VAC.

  3. 3

    Inspect the control circuit transformer.

  4. 4

    Check the wiring connections to the control transformer and the module.

Browse all codes in this manual (55)
Verified technical data. Last updated: April 2026

Related Faults

ALERT LED * flashes Yellow (misreported)Yellow ALERT LED * flashes (misreported) — Welded Contactor checkALERT LED 2 flashes YellowYellow ALERT LED 2 flashes — System pressure trip or compressor overloadALERT LED 3 flashes YellowYellow ALERT LED 3 flashes — Compressor short cycling
Source: Bryant Comfort Alert Diagnostic Module
Open Manual (Page 29)Search more codes in this manual