Carrier · Air Conditioners & Heat Pumps
This fault means the 670psi high pressure switch has activated, safely disabling system operation. It can occur due to rapid pressure spikes or a fault in the high-pressure switch's wiring harness during high-pressure events. The system will not attempt to restart until discharge pressure drops below 425 PSIG.
Click steps to track your progress.
Wait for the system to cool down naturally; operation will resume once discharge pressure falls below 425 PSIG.
Ensure the high pressure switch (HPS) is securely connected to the VFD.
Inspect the wire harness connected to the HPS and VFD for any signs of breaks, shorts, or loose connections.
If the fault persists, contact a qualified technician as it may indicate an internal pressure issue or faulty switch.