Carrier · Air Conditioners & Heat Pumps
The system has detected a low compression ratio that cannot be adjusted by Automatic Envelope Management (AEM), causing a shutdown. Before this fault, AEM attempts to increase compression ratio by reducing outdoor fan speed (cooling only) and then increasing compressor speed. Repeated occurrences can lead to a lockout.
Click steps to track your progress.
Allow the system to attempt self-correction through AEM (reducing fan speed, increasing compressor speed).
If the problem persists or recurs, contact a qualified technician.
Have a technician check the compressor's ability to increase pressure and the system's refrigerant charge.