This fault indicates that the signal wire for pressure transducer P1 (codes 57-xx) or P2 (codes 58-xx) is 'open,' meaning it's returning more than 4.5V DC. This typically occurs if the sensor wire is disconnected, causing the PCM to pull the signal voltage to +5V DC.
Click steps to track your progress.
Visually inspect the wiring harnesses for pressure transducers P1 and P2, focusing on the green signal wire (GRN).
Ensure the sensor wire is securely connected to both the transducer and the PCM board.
Verify that the red power wire (RED) is supplying +5V DC and the green signal wire (GRN) is returning a DC voltage between 0.5-4.5 VDC.
If connections and voltages appear correct, the pressure transducer itself may be faulty and require replacement by a technician.