Carrier · VVT-1T System
A Comfort Trend (CT) error is a transparent error detected by the slave thermostat, indicating difficulty in maintaining the desired temperature conditions in its zone. The thermostat does not display this error directly; it must be accessed and cleared using the PC Command Center software. It signifies that the zone temperature is not improving or is worsening over time.
Click steps to track your progress.
Check and adjust the Damper Maximum Open Position (rotary switch position 5) or balancing dampers for pressure-dependent zones. Set to 15 for full open.
Verify and adjust the Airflow Set Point for pressure-independent zones to a higher value, ensuring Damper Maximum Open Position is set to 15 and no balancing dampers reduce airflow.
Inspect the ductwork to the zone for loose connections or poor insulation that could reduce air volume or affect temperatures.
For VVT systems, check the bypass controller configuration to ensure it's not causing low system static pressure.
Verify the performance of the supply-air fan to ensure it produces adequate supply air and static pressure.
Check the temperature of the airflow into the zone; if it's outside design conditions, inspect the main equipment operation.