Carrier · VVT-1T System
This error means the slave thermostat is trying to close the damper blade, but the electronic position sensor does not register that the damper is in the full-closed position. This can be due to a mechanical issue or a sensor problem.
Click steps to track your progress.
Check the damper for any mechanical binding, such as obstructions or a bent blade, and remove them.
Align the damper and the actuator so that both fully closed positions coincide. Ensure the slave thermostat's Ventilation and Minimum Damper Position setting is zero before alignment.
Disconnect the slave thermostat from the wiring connector board. Using a screwdriver, turn the traveler screw on the stepper motor until the traveler arm is midway, then reconnect the slave thermostat.
Check for excessive inlet static pressure that might be preventing the damper from closing properly.
Verify the configuration of the slave thermostat's Clockwise Open Damper Modulation option. For Carrier dampers that open counterclockwise, this option should be OFF.
Check the wiring between the damper actuator and slave thermostat for continuity, especially the green wire. Test by connecting the slave thermostat directly at the damper board.