Carrier · VVT-1T System
This error indicates that the airflow sensor is reading a value outside its normal operating range. The specific cause can vary depending on whether a VS/ZVS-01 airflow sensor or a PS pressure sensor is installed.
Click steps to track your progress.
For VS or ZVS-01 sensors, check the zone velocity sensor reading with the supply-air fan off. It should be between 00 01 and 00 10. If not, calibrate using the slave thermostat (rotary switch position 8) or Device Calibration software.
For VS or ZVS-01 sensors, if calibration fails, check the voltage between the white and red wires at the damper actuator. It should read 10 VDC. If not, the damper board may be defective.
For VS or ZVS-01 sensors, if voltage is good at the actuator, check the same voltage at the sensor. If not 10 VDC, the field wiring is defective.
For PS Pressure Sensors, check for excessive static or differential pressure at the sensor. Ensure it's not exceeding the maximum rated pressure for your sensor model.
For PS Pressure Sensors, check the hose connections from the PSP pressure pickup to the PS sensor for correctness and integrity.
For PS Pressure Sensors, verify that the wiring from the sensor to the damper actuator is complete and well-connected. Ensure 'O' connections are not used or shorted to ground.