Carrier · VVT-1T System
A Storage Failure (SF) error, specifically SF 06, indicates that the slave thermostat's stored Comfort Set Point Limiting settings have been corrupted or lost. The system will default to 66°F (Cooling) and 80°F (Heating). These limits prevent users from setting temperatures outside a specified range.
Click steps to track your progress.
Establish communications with the slave thermostat using the PC Command Center software.
Initiate a Device Inquiry for the slave thermostat to verify its current settings.
Perform the 'Modify Device Information' command and navigate to the Comfort Set Point Limiting settings.
Re-enter the desired Cooling and Heating limit values.
Press F1 to 'Perform Update' and wait for acknowledgement to save the new settings.
Exit the configuration menu and program, then verify the limiting settings are correctly stored.