Carrier · VVT-1T System
A Storage Failure (SF) error, specifically SF 11, indicates that the slave thermostat's stored System Options #4 settings have been corrupted or lost. This includes options like Setback Programming Lock and Meter Setback Override. Defaults are mostly OFF, except Rotary Switch Lock which is ON.
Click steps to track your progress.
Establish communications with the slave thermostat using the PC Command Center software.
Initiate a Device Inquiry for the slave thermostat to verify its current settings.
Perform the 'Modify Device Information' command and navigate to the System Options #4 settings.
Re-enter the correct settings for each option (e.g., Setback Programming Lock, Local Setback Override Lock).
Press F1 to 'Perform Update' and wait for acknowledgement to save the new settings.
Exit the configuration menu and program, then verify the System Options #4 are correctly stored.