A Storage Failure (SF) error, specifically SF 12, indicates that the slave thermostat's stored Setback/Comfort Program schedule has been corrupted or lost. The system will default to a program of 6 a.m. (ON, M-S) and 6 a.m. (OFF, M-S). This schedule dictates when the system switches between comfort and setback modes.
Click steps to track your progress.
Establish communications with the slave thermostat using the PC Command Center software.
Initiate a Device Inquiry for the slave thermostat to verify its current settings.
Perform the 'Modify Device Information' command and navigate to the Setback/Comfort Program settings.
Re-enter the desired schedule for the zone, including ON and OFF times for weekdays and weekends.
Press F1 to 'Perform Update' and wait for acknowledgement to save the new settings.
Exit the configuration menu and program, then verify the program schedule is correctly stored.