Carrier · VVT-1T System
A Storage Failure (SF) error, specifically SF 23, indicates that the slave thermostat's stored Airflow Sensor Error Correction (for SSP-01E) value has been corrupted or lost. The system will default to a Mid-Range Value. This calibration corrects readings from the SSP-01E airflow sensor.
Click steps to track your progress.
Establish communications with the slave thermostat using the PC Command Center software.
Initiate a Device Inquiry for the slave thermostat to verify its current settings.
Perform the 'Modify Device Information' command and navigate to the Airflow Sensor Error Correction (SSP-01E) setting.
Re-enter or reset the appropriate calibration value for the SSP-01E airflow sensor.
Press F1 to 'Perform Update' and wait for acknowledgement to save the new setting.
Exit the configuration menu and program, then verify the calibration is correctly stored.